CompactFloor® PRO 12

 

Floor installation

Download floor installation as PDF

Basic installation

Advisable for upper floors and for lower installation heights

Basic installation underfloor heating with CompactFloor PRO 12
  • CompactFloor® PRO 12
    12 mm
  • GreenLine system panel + MVR heating pipe
    30 mm
  • Edge insuation strips
  • Total installation height approx.
    ≥ 42 mm

Extended installation with additional insulation

Advisable for the ground floor or cellar and for larger installation heights

Extended installation underfloor heating with CompactFloor PRO 12
  • CompactFloor® PRO 12
    12 mm
  • GreenLine system panel + MVR heating pipe
    30 mm
  • Additional insulation
    ≥ 30 mm
  • Edge insulation strips
  • Total installation height approx.
    ≥ 72 mm

 

Suitable floor coverings

suitable for tiles, design flooring, carpet, laminate and parquet

 

Technical data Basic installation Extended installation
Heating circuit length ø 80 – 90 m (~ 15 m²) | max. 110 m
Additional insulation 20 – 60 mm wood fibre insulation ≥ 150 kPa
Weight 25 - 32 kg / m² (without floor covering)
Surface load | Point load 2.0 kN / m² | 2.0 kN 2.0 kN / m² | 2.0 kN
Minimum thermal conductivity resistance R ≥ 0.75 m²K / W
DIN EN 1264: Floors in mezzanine floors
≥ 1.25 m²K / W
DIN EN 1264: Floors on ground floors / cellars

 

Important information
Base requirements
(accord. DIN 18202 table 3, line 4)
Bases must be level, stable and able to take a load.
Unevenness > 3 mm at 1 m length must be compensated.
Compensation of unevenness
(according to degree of unevenness)
0 – 10 mm: Floor levelling paste
10 – 50 mm: Floor levelling paste, thin screed, dry filling
from 40 mm: Bulk filling, light concrete
Special aspects Process CompactFloor PRO with jig saw.
Max tile format 0.60 x 0.60 m

 

Performance table

Floor covering Room temperature Heating water temperature
30°C 35°C 40°C 45°C
W / m² ST W / m² ST W / m² ST W / m² ST
Floor covering
Rλ,B = 0.00 m² K / W
Tiles
20 °C 48.5 24.5 73.6 26.8 98.5 29.1 123.4 31.4
24 °C 27.9 26.6 53.5 29.0 78.6 31.3 103.5 33.6
Floor covering
Rλ,B = 0.05 m² K / W
Laminate, needle punched flooring, PVC flooring
20 °C 37.4 23.5 56.8 25.3 76.1 27.0 95.3 28.8
24 °C 21.5 26.0 41.3 27.8 60.7 29.6 79.9 31.4
Floor covering
Rλ,B = 0.10 m² K / W
Carpet
20 °C 30.5 22.8 46.3 24.3 62.0 25.7 77.7 27.2
24 °C 17.6 25.6 33.7 27.1 49.5 28.6 65.1 30.0
Floor covering
Rλ,B = 0.15 m² K / W
Ready-made parquet, wooden floor boards
20 °C 25.8 22.4 39.1 23.6 52.3 24.8 65.6 26.1
24 °C 14.8 25.4 28.4 26.6 41.7 27.9 55.0 29.1
W / m² – System heating output
ST – Surface temperature

 

Installation

 

Sample laying plan

Sample laying plan underfloor heating

Download floor installation as PDF

Contact

If you have any questions, feel free to contact us:

support[at]quick-tec.com

Business Hours

Our QuickTec Online-Shop is available 24 hours a day.

Our support hotline is available Mo-Fr: 9am to 4pm (49) 30 | 577 0188 40